Flexible Conduit Products
Alflex™ Type RWA Reduced Wall Aluminum Flexible Metal Conduit
Aluminum Flexible Metal Conduit. High Strength Aluminum Alloy Strip. 5/16" is UL Recognized Component. UL Listed in sizes 3/8" to 3".
Application
Alflex™ Type RWA (Reduced Wall Aluminum) Flexible Metal Conduit is suitable for the following installations:
Environmental air-handling spaces per NEC 300.22(C)
Power and lighting branch circuit conductors and cables for connecting receptacles, luminaires, equipment, office partitions, etc.
Metal raceway for wires and cables per NEC (ANSI/NFPA-70) Article 348
Motor feeder, branch, and control circuit conductors and cables
Class 1, Class 2, Class 3 Remote-control, signaling, and power-limited circuit conductors and cables
Fire alarm system conductors and cables of power-limited or non-power-limited fire alarm circuits
Voice, data, communications and video cables including CATV and optical fiber cables
Concealed or exposed installations per NEC 348 and the applicable NEC provisions
Elevators, hoistways, and escalators per NEC 620.21
Listed wired fixtures per NEC 410.77(C)
Raised floors for connection of information technology per NEC 645.5(D)(2) and 645.5(D)
Places of assembly and theaters per NEC 518 and 520
Cranes & hoists per NEC 610.11(C)
As a grounding conductor for lengths up to 6 feet (20A max) as per NEC 250.118(5)
Electric signs and outline lighting per NEC 600.7, 600.31 (1000 volts or less), and 600.32 (>1000 volts)
Hazardous location, Class 1, Div. 2, for flexible connectors only per NEC 501.10(B)(2) & 501.30(B)
UL 1, 2, & 3 Hour Through-Penetration Firestop Systems: C-AJ-1462, C-AJ-1463, C-AJ-1464, W-L1308, and W-L-1309
Titan®2 Type CB Liquidtight Flexible Metal Conduit
Computer Blue Liquidtight Flexible Metal Conduit. Easy to Identify Blue Jacket for Computer Applications. UL/CSA Listed. Oil-Resistant. Sunlight-Resistant. Temperature Rated -55°C to 80°C.
Application
Titan®2 Type CB Liquidtight Flexible Metal Conduit is suitable for the following installations:
Under raised floors in data processing areas per NEC 645.5(D) & 645.5(D)(2)
For the installation and protection of electrical conductors in circuits of 600 Volts nominal, or less
Where the conditions of installation, operation, or maintenance require flexibility or protection from liquids, vapors, solids, or weather
Used in industrial and commercial applications for conveyors, blowers, cranes, air conditioners, machine tooling and lubrication equipment
Applications requiring movement, crossover connections, or tight bends
Exposed or concealed locations
For flexible connections to swimming pool, spa, and hot tub motors per NEC 680.21(A)(3) & 680.42(A)(1)
Electric signs and outline lighting supply and secondary-circuit per NEC 600.31 (1000 Volts or less) & NEC 600.32 (over 1000 Volts)
Permitted for equipment grounding in sizes 3/8" through 1-1/4" in lengths not exceeding 6 feet per NEC 250.118(6)
Floating building feeders and services per NEC 553.7(B)
Boatyards & Marinas in accordance with NEC 555.13
Cranes & Hoists in accordance with NEC 610.11(C)
For Elevator, Dumbwaiters, Escalators, Moving Walks, Wheel Chair Lifts & Stairway Chair Lifts in accordance with NEC 620.21 (where expressly permitted)
Service entrance in lengths up to six feet per NEC 230.43(15)
Ultratite® Type NM
Liquidtight Flexible Nonmetallic Conduit. UL/CSA Listed. Oil-Resistant. Sunlight-Resistant. Crush-Resistant. Temperature Rated -30°C to 80°C.
Application
Ultratite® Liquidtight Flexible Nonmetallic Conduit is suitable of the following installations:
For the installation and protection of electrical conductors
Motor circuits - for conductors of motor feeders, branch and control circuits
Where the conditions of installation, operation, or maintenance require flexibility or protection from liquids, vapors, solids, or weather
Agricultural buildings per NEC® 547.5
Used in industrial and commercial applications for conveyors, blowers, cranes, air conditioners, machine tooling and lubrication equipment
Exposed or concealed installations
Applications requiring movement, crossover connections, or tight bends
For direct burial and encased in concrete
For flexible connections to swimming pool, spa, and hot tub motors per NEC® 680.21(A)(3) & 680.42(A)(1)
Electric signs and outline lighting supply and secondary-circuit conductors per NEC® 600.7, 600.31 (1000 volts or less) & 600.32 (over 1000 volts)
Hazardous locations - see Additional Applications Section on the following page for more details